Predicting Flashover Voltage on Polluted Porcelain Insulator

Bodise Lebrun Bolou-Sobai, Danfebo Franklin Ayebagbalinyo, Charles Godspaower, Idongha


Abstract


This paper developed a simple linear regression model to predict the flashover voltage of polluted porcelain insulators based on Equivalent Salt Deposit Density (ESDD). The developed model Y = 58.75 – 63.69(ESDD) demonstrated strong predictive capability, with a correlation coefficient (R) of 95.28%, indicating near-perfect alignment between predicted and experimental values. An R² value of 90.78%, confirming that ESDD explains most of the variability in flashover voltage. Statistically significant results (p-value (0.0471), F-statistic (19.70)), validating the model’s reliability. It is simple yet accurate predictive model bridging the gap between laboratory experiments and field applications in pollution flashover analysis. This analysis demonstrates that ESDD is a critical predictor of flashover.


keywords:

Regression Analysis, Porcelain Insulator, Voltage Flashover, Prediction,


References:


Ali, S., Rahisham, A., Waheed, G, Samir, A., & Salem, A. (2021). Prediction Flashover
Voltage on Polluted Porcelain Insulator Using ANN. Computers,Materials & Continua,
3756-3771.
Banik, A., Dalai, S., & Chatterjee, B. (2015). Studies the effect of Equivalent Salt Deposit
Density on leakage current and flashover voltage of artificially contaminated disc
insulators. In 2015 1st Conference on Power, Dielectric and Energy Management at
NERIST (ICPDEN) (pp. 1–5). IEEE.
Chakraborty, R. (2017). Studies on Silicone Rubber Insulators used for High Voltage
Transmission. Department of Electrical Engineering, Indian Institute of Science,
Bangalore
Chandrashekhar, B., & Pradipkumar, D. (2016). Predictionofpollutionflashover voltages of
ceramic string insulators under uniform and nonuniformpollutionconditions.
JournalofElectricalSystemsandInfor mationTechnology, 270-281.
Dong, B., Zhang, Z., Xiang, N., Yang, H., Xu, S., & Cheng, T. (2020). AC flashover voltage
model for polluted suspension insulators and an experimental investigation in salt fog.
IEEE Access, 8, 187411-187418.
Douar, M. A., Beroual, A., & Souche, X. (2015). Degradation of various polymeric materials
in clean and salt fog conditions: measurements of AC flashover voltage and assessment
of surface damages. IEEE Transactions on Dielectrics and Electrical Insulation, 22(1),
391-399.
Genço?lu, M. T., & Cebeci, M. (2008). The pollution flashover on high voltage insulators.
Electric Power Systems Research, 78(11), 1914–1921.
Gouda, O. E. S., El Dein, A. Z., & El-Tayeb, A. (2014). Prediction of flashover voltage and
dry band location for polluted ceramic insulators using dynamic open-model. J. Energy
Power Sources, 1(6), 304-313.
Hussain, M. M., Farokhi, S., McMeekin, S. G., & Farzaneh, M. (2017). Mechanism of saline
deposition and surface flashover on outdoor insulators near coastal areas part II: Impact
of various environment stresses. IEEE Transactions on Dielectrics and Electrical
Insulation, 24(2), 1068-1076.
Kumar, K., & Maheswari, R. V. (2024). An experimental study of the flashover performances
of outdoor high-voltage polymeric insulators under fan-shaped pollution and dry band
location. Electrical Engineering, 1-17.
Salem, A. A., Lau, K. Y., Rahiman, W., Abdul-Malek, Z., Al-Gailani, S. A., Mohammed, N.,
... & Al-Ameri, S. M. (2022). Pollution flashover voltage of transmission line
insulators: Systematic review of experimental works. IEEE Access, 10, 10416-10444.
Sanyal, S., Aslam, F., Kim, T., Jeon, S., Lee, Y. J., Yi, J., ... & Koo, J. B. (2020). Deterioration
of porcelain insulators utilized in overhead transmission lines: A review. Transactions
on Electrical and Electronic Materials, 21, 16-21.
Yousaf, M., Iqbal, T., Hussain, M. A., Tabish, A. N., Haq, E. U., Siddiqi, M. H., ... &
Mahmood, H. (2022). Microstructural and mechanical characterization of high strength
porcelain insulators for power transmission and distribution applications. Ceramics
International, 48(2), 1603-1610.
Zelalem, B., & Mamo, M. (2020). Assessment of external insulation problems related to
pollution and climatic conditions in Ethiopia. IEEE Electrical Insulation Magazine,
36(4), 36-46.


DOWNLOAD PDF

Back


Google Scholar logo
Crossref logo
ResearchGate logo
Open Access logo
Google logo